Features

  • Identifies 3-phase sequence and open phase check
  • Motor shaft rotation indication protected by CAT III circuitry
  • CAT III 600V rated for both testing segments
  • Meets current EN61010 safety requirements, CSA, EN61557-7
  • Supplied with three CAT III rated color coded large alligator clips and test leads
  • Zippered carrying case for portability
 
General Specifications
 
Operating Environment 0°C to 40°C at <80 % R.H.
Power Single standard 9 V battery
NEDA 1604
JIS 006P
IEC 6F22
Battery life Approximately 200 hours typical with carbon-zinc battery
Low battery indication The BATT LED does not come ON when TEST button is pressed
Dimensions (H x W x D) 153 mm x 72 mm x 35 mm (6.02 x 2.83 x 1.37 in)
Weight Approximately 218 g (7 oz) including battery.
Environment Indoor use
Altitude 2000 m (6561 ft.)
Overload protection 600 V ac
Agency Approvals CE, cCSAus
Safety Conforms to EN61010-1:2001
CAT III 600V, Pollution degree 2, Class 2
CSA 22.2 -1010-1
EN61557-7
EMC Conforms to EN61326-1. This product complies with requirements of the following European Community Directives: 89/ 336/ EEC (Electromagnetic Compatibility) and 73/ 23/ EEC (Low Voltage) as amended by 93/ 68/ EEC (CE Marking). However, electrical noise or intense electromagnetic fields in the vicinity of the equipment may disturb the measurement circuit. Measuring instruments will also respond to unwanted signals that may be present within the measurement circuit. Users should exercise care and take appropriate precautions to avoid misleading results when making measurements in the presence of electronic interference.
 
Electrical Specifications
 
Phase Sequence
Input Voltage 3 phase to phase inputs 100 V ac to 600 V ac max.
Frequency 45 to 70 Hz
Operating Time 10 minutes ON maximum at 600 V ac
10 minutes OFF minimum at 600 V ac
3-Phase load Approx. 7 mA per phase of ac power source
Motor Rotation
Operating Time 10 minutes ON maximum
10 minutes OFF minimum.
Motor Rotation tester field 14 mA of 9 V battery


 

 

Currently there are no reviews for this product. Share your opinion with others, be the first to write a review.